Power Distribution Units (PDU)
Power Distribution Units
Odyssey Power provides state-of-the-art power distribution units from top manufacturers that can be customized to fit your requirements:
- Subfeed and panelboard monitoring
- 42 circuit panelboards rated up to 400A
- Subfeed breakers up to 800A
- I-line panelboards up to 1200A
- EPO options
- SNMP Communications
Complete the form for more information:
PDU, 3-Phase Models
On-Line Services Include:
- Perform a temperature scan on all breakers, power connections, fuses and associated controls. Repair and/or report all abnormal readings.
- Perform a complete visual inspection of the equipment including subassemblies, wiring harnesses, contacts, cables and major components.
- Inspect the control cabinet for accumulations of dust and/or debris. Clean as required.
- Record all voltage and current meter readings on the meter panel.
- Measure and record all voltage and current readings at the input and output of unit.
- Verify that all front panel meter readings are correct. Calibrate if required.
- Verify that indicator lamps are working.
- Verify auto or manual restart selection.
Off-Line Services Include Above, Plus:
- With customer’s permission, open the input circuit breaker to the PDU. Note: This will remove all power to the load.
- Physically check all nuts, bolts, screws and connectors for tightness and heat discoloration.
- Physically check control wires, ribbons and connectors for correct and secure installation.
- Measure and record all low-voltage power supply levels.
- Verify that all branch circuit breakers are installed correctly and are secure.
- Remove dust from circuit cards and other sensitive components.
- After completion of the preventive maintenance routine, verify that all branch breakers are closed and ready for re-energizing.
- Before closing the input circuit breaker of the PDU, verify that UPS is in bypass mode.
- Review system performance with customer to address any questions and to schedule any repairs.